Heating cables : Range B800

Function :

Self-regulating heating cable temperature for frost protection of pipes, equipments and citerns.

  • Offset heat losses.
  • Decrease heat insulation thickness.
  • Ensure the proper flow of fluids, prevent degradation of liquid.
  • Avoid freeze creation on pipes, equipment and citterns.
  • Remove condensates.
  • No maintenance.

1 Electrical semi-conductive polymer
2 Nickel Plated Copper Strand
3 Electric Insulation with polyolefin
4 Aluminium/polyester tape shielding with overlap 8 x diameter 0.4 mm
5 Thermoplastic Outer jacket, Thermoplastic elastomer, Thermoplastic polymer vulcanized, polyurethane

Features :

Supply electrical voltage : 230Vac

Maximum rating temperature with power on : 50°C
Maximum exposure temperature power off : 65°C
Temperature classification (according to European Standard EN 50014) : T6 (85°C)
Minimum installation temperature : -20°C

Minimum bend radius at -20°C : 30 mm
Minimum bend radius at 20°C : 13 mm

Cable theoretical weight : 90 kg/km

Maximum conductor resistance at 20°C : 15,29 Ohms/km
Electrical protection resistance : 14 Ohms/km
Diameter conductor stranded nickelled copper : 1.43 mm
Section conductor : 1.23 mm²

Color : Black

Properties :

Application :

Area classification
Ordinary area

Nature of pipe
Steel
Painted surface
Stainless steel
Plastic

Chemical resistance
Elastomer thermoplastic
Polyolefin

Electric protection
Self-regulating cables must be installed with a circuit breaker or a differential magneto interrupter (curve C or K) 30mA caliber in order to assure physical people and self-regulating tape protection. (D NFC 15-100 Norm).

Indispensable accessories for installation :
Endings kit (KT01), connection case (BR03), aluminium adhésive tape (A01), Thermostat (TH01).

Installation accessories :
Case support (SB01), stainless steel collars (CL01).








- Maintain fluids or liquids in temperature



Protect your tanks, reservoirs, gutters, hoses and pipes with heating wires. Keep fluid or liquid in temperature with self-regulating heating cables.